AHU Psychrometric & KPI Calculator | TheHVACLab Technologies
TheHVACLab Technologies

AHU Psychrometric & KPI Calculator

ASHRAE Compliant SI Units Field-Ready
Enter DB + RH (or DB + WB) for each state point. The calculator computes enthalpy, humidity ratio, ADP, BPF, SHR, and coil capacity. Minimum required: State Points 3 (Mixed Air) and 5 (Supply Air) for coil analysis.
Point DB (°C) RH (%) WB (°C)
m³/hour — used for capacity calculations
Affects atmospheric pressure & psychrometrics
Enter values and click Calculate
TheHVACLab™ AEI Framework — 4 proprietary KPIs measurable with basic field instruments. Each KPI includes a benchmark range and RAG status.
KPI-1: AHU Efficiency Index (AEI)
AEI = Q_coil / (Fan kW + Pump kW)
KPI-2: Coil Performance Index (CPI)
CPI = (T_EAT – T_LAT) / (T_EAT – T_ADP) × 100%
KPI-3: Airflow Effectiveness Score (AES)
AES = (Q_act/Q_des) × (ΔP_clean/ΔP_curr) × 100%
KPI-4: System Energy Intensity (SEI)
SEI = Total kW / Floor Area (m²) → W/m²
Calculate Specific Fan Power (SFP), fan efficiency, VFD savings potential, and motor power from field measurements. ECBC / ASHRAE 90.1 benchmarks applied automatically.
Fan Power Inputs
VFD Savings Estimator
Fan Power ∝ Speed³ (Affinity Law)
Savings % = 1 – (n_target/n_current)³
Quantify energy penalties from 5 common AHU faults. Enter measured vs. design values — the calculator outputs kW penalty, annual kWh loss, and ₹ cost per fault.
Dirty Filter Penalty
Penalty = Q × ΔΔP / (η_fan × η_motor × 1000)
Over-Ventilation Penalty
Penalty = ṁ_OA × (h_OA – h_RA) / COP
ṁ = Q × 1.2 kg/m³
Low ΔT CHW Syndrome Penalty
Flow ratio = ΔT_des / ΔT_act
Extra pump kW ≈ Pump kW × (ratio² – 1) × 0.5
Excess SFP Penalty
Penalty = (SFP_act – SFP_target) × Airflow (L/s) / 1000
Common Parameters
Enter live field measurements and the FDD engine will auto-flag faults against 20 diagnostic rules. Rules are prioritized by energy impact.
Airflow & Pressure
Temperature & Coil
Ventilation & Controls